Standard operating conditions
Normal inlet pressure: 7 bar(g),
Normal inlet temperature : 35°C
Pressure dew point: -40°C
Maximum operating pressure: 10bar
Minimum operating pressure: 4bar
Maximum inlet temperature: 50°C
Minimum inlet temperature: 10°C
Standard electrical supply: 380V/3Ph/50Hz
Model
|
Flow Capacity
|
Heater (kw)
|
Dimensions
|
Air Conn.
|
Weight
|
m3/min
|
CFM
|
L(mm)
|
W(mm)
|
H(mm)
|
(BSP)
|
(kg)
|
KXR-5
|
0.7
|
25
|
0.9
|
690
|
500
|
915
|
1/2”
|
120
|
KXR-10
|
1.6
|
56
|
0.9
|
690
|
500
|
1298
|
1”
|
190
|
KXR-20
|
2.6
|
92
|
1.5
|
780
|
500
|
1324
|
1”
|
280
|
KXR-30
|
3.8
|
134
|
1.5
|
860
|
540
|
1350
|
1”
|
320
|
KXR-60
|
7.0
|
247
|
2.4
|
1010
|
700
|
1558
|
1 1/2”
|
480
|
KXR-75
|
8.5
|
300
|
2.4
|
1010
|
700
|
1785
|
1 1/2”
|
540
|
KXR-100
|
11.5
|
406
|
4.5
|
1240
|
800
|
2232
|
2”
|
650
|
KXR-120
|
13
|
476
|
4.5
|
1240
|
800
|
2232
|
2”
|
690
|
KXR-150
|
17
|
600
|
5.4
|
1280
|
860
|
2360
|
DN65
|
780
|
KXR-200
|
23
|
812
|
7.5
|
1320
|
860
|
2477
|
DN65
|
920
|
Flow capacity is based the following conditions:
air FAD 20°C/1 barA, pressure 7 bar(g), relative humidity 100%,
air inlet temperature 35°C, pressure dew point -40°C
Inlet Air Pressure Correction- C1
bar g
|
4.0
|
5.0
|
6.0
|
7.0
|
8.0
|
9.0
|
10
|
11
|
12
|
13
|
14
|
Factor
|
0.62
|
0.77
|
0.9
|
1.0
|
1.09
|
1.19
|
1.24
|
1.31
|
1.37
|
1.42
|
1.47
|
Inlet Air Temperature Correction- C2
bar g
|
25
|
30
|
35
|
40
|
45
|
50
|
Factor
|
1.12
|
1.06
|
1.0
|
0.93
|
0.86
|
0.78
|
Example Calculations:
KXR-120 corrected for 8 bar + 40℃
Corrected Capacity=Rated Capacity x C1 xC1=13.5Nm3/minx1.09x0.93=13.77Nm3/min